Contact Us CH | EN

EN 50288-7 / BS5308-1

Home > Products > Instrumentation Cable > EN 50288-7 / BS5308-1

Individually & Overall Screened Unarmored PE Insulated Instrumentation Cable
  • Introduction
  • Specifications
  • Dimensions

Standards

1. Reference Standard: BS5308-1
2. Rated voltage: 300V
3. Recommended bending radius:
12 x Cable Outer Diameter (during installation)
8 x Cable Outer Diameter (after installation)

Applications

Generally used within industrial manufacturing plants for communication, data and voice signal transmission and also used for the interconnection of electrical equipment and instruments, typically in petroleum industry.

Characteristics

1. Conductor with high quality copper, low signal transmission attenuation
2. Insulated with PE, anti-aging, non-toxic and other characteristics can be customized.
3.Individual & overall screened with aluminum foil, effectively blocking the external electromagnetic interference.
4. Sheath material for high-quality PVC, anti-aging, wear resistance, low-temperature resistance, waterproof, anti-oil, anti-chemical corrosion, non-toxic and other characteristics can be customized.

 

Nominal  CSA    (mm2) Max. CR    @ 20 Approximate Current Carrying Capacity Max. Capacitance C-C (IND,O/A SCR) Max. Capacitance C-S (IND,O/A SCR) Attenuation @1kHz between 600Ω Terminations      (I/O SCR) Characteristics Impedance          @ 1kHz           (I/O SCR) Inductance    @ 1kHz (mH/km) L/R Ratio @ 1kHz (μH/Ω)
0.50 38.4Ω/km 2~3.5 A 145pF/m 240pF/m 0.11dB/100m 300Ω 1.00 13.7
0.75 24.5Ω/km 3~7.5 A / / / / 0.98 20.0
1.00 18.1Ω/km 4~10.0 A / / / / 0.97 27.7
1.50 13.6Ω/km 5~13.1 A 200pF/m 300pF/m 0.09dB/100m 150Ω 0.95 36.5

Shanghai Aipu Waton Electronic Technology(Group)Co.,Ltd